Overview
The microprocessor based CE mark 12 Zone conventional fire alarm control panel, the system has 20 X 4 LCDcharacter with alpha numeric touch key pad, 12 zones detection circuit, 3 common programmable potential free contacts & 2 common NAC sounder output, inbuilt Rs-485 for Networking – TCP/IP, peer to peer & repeater connectivity, central monitoring facility, inbuilt RTC with Event logs, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.
RE-900 Series fire alarm control panel is designed with unique protocol to be used for small, medium & Large establishments, Schools, hospitals, hotels, banks, residential / commercial building, and small scale industries. The system is user friendly with includes all standard to ensure ease for use and high reliability.
Special Feature:
- Complies with UL -864 and NFPA-72.
- 20 x 4 Dot Matrix LCD Display.
- Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
- Standby (battery) backup 24v DC power supply with builtin charger.
- Touch Keypad for user friendly operation.
- Epoxy powder coated finish.
- Class- B, Style B / C initiating device circuit (IDC).
- All zones accept smoke detectors and any normally open contact device.
- Class B Notification Appliance Circuits (NAC).
- NAC shall be programmed as auto silence / Silence Inhibit.
- Error free Fire / Fault status in unambiguous colored LED indication.
- 1000 Event storage with RTC.
- Main, Standby status with audible and visual indication.
- Two Form C relays for fire and fault.
- Resettable / Steady 24V D.C. Output.
- RS 485 Communication facility.
- TCP/IP facility (Optional)
- MODBUS for BMS integration (Optional).
- PC software (optional)
- External Zone Wise Sounder/Contact via RS 485 (Optional).
- All field wiring circuits are supervised.
- Zone Isolation facility with loop voltage cut off.
- Zones available : 12, 16, 20, 24, 32, 48, 64,96 and 128.
- Facility to connect Public Address System (PA) through RS-485 Communication.
- Peer to Peer network facility.
- Maximum 16 panels can be connect in a Single Network.
Electrical Specification
Initiating Device CircuitsAll zones are
Class B Style B/C operation (Programmable).
Normal Operating Voltage : 14 – 21 VDC.
Alarm Current : 15 – 30mA.
Short Circuit Current : 45mA Maximum.
Loop resistance : 100 ohms Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Standby Current : 7mA (2.5mA for Detectors)
Notification Appliance CircuitsClass B Style – Y wiring
Operating Nominal Voltage : 24VDC
Special Application Current : from 12 Zone Upto 64Zone
NACs : 2 Amps (1 A per circuit) Current above 64Zone
NACs : 4 Amps (1 A per circuit)
Line Drop : 1.8V
End-Of-Line Resistor : 4K7, 1/2watt
Standby Power 24V D.C Quiescent current : 120 mA | |
|
|
| |
|